🚚 We Ship Worldwide! Get your order delivered anywhere.🌍

Brand New Partnership with DeLock!

Ifm  |  SKU: IF-SV4200-E  |  Barcode: DOES NOT APPLY

Ifm SV4200 Sv Vortex Flowmeters With Display For Water Based Media

$448.33 USD
Shipping calculated at checkout.

Ifm SV4200 Sv Vortex Flowmeters With Display For Water Based Media is backordered and will ship as soon as it is back in stock.


🚚 We Ship Worldwide! Get your order delivered anywhere.

🌎 No Borders, Just Shipping! We deliver to your doorstep—anywhere.

Delivery And Shipping

Both Standard and Express shipping options are available at checkout.

Subscribe to our newsletter

Sign up for exclusive offers.

Industrial Automation Parts is only an authorized distributor for DeLock and is not authorized for any other manufacturers. Manufacturer's warranty and support do not apply. Our IAP warranty of three months is applicable.

Product characteristics
Number of inputs and outputs Number of digital outputs: 2
Measuring range
1...20 l/min 0.06...1.2 m³/h
Process connection threaded connection G 1/2 DN8
Application
System gold-plated contacts
Application for industrial applications
Media water; glycol solutions; Coolants
Medium temperature [°C] -10...90
Pressure rating [bar] 12
Pressure rating [MPa] 1.2
Note on pressure rating
up to 40 °C
MAWP (for applications according to CRN) [bar] 3.9
Electrical data
Operating voltage [V] 18...30 DC
Current consumption [mA] < 30
Min. insulation resistance [MΩ] 100; (500 V DC)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] < 3
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 2
Outputs
Total number of outputs 2
Output signal switching signal; frequency signal; IO-Link; (configurable)
Electrical design PNP/NPN
Number of digital outputs 2
Output function normally open / closed; (configurable)
Max. voltage drop switching output DC [V] 2.5
Permanent current rating of switching output DC [mA] 100
Short-circuit protection yes
Overload protection yes
Measuring/setting range
Measuring range
1...20 l/min 0.06...1.2 m³/h
Display range
0...24 l/min 0...1.44 m³/h
Resolution
0.1 l/min 0.005 m³/h
Set point SP
1.2...20 l/min 0.07...1.2 m³/h
Reset point rP
1...19.8 l/min 0.06...1.19 m³/h
Frequency end point, FEP
4...20 l/min 0.24...1.2 m³/h
In steps of
0.1 l/min 0.005 m³/h
Frequency at the end point FRP [Hz] 100...1000
Measuring dynamics 1:20
Temperature monitoring
Measuring range [°C] -10...90
Display range [°C] -30...110
Resolution [°C] 0.5
Set point SP [°C] -9...90
Reset point rP [°C] -10...89
In steps of [°C] 0.5
Frequency start point, FSP [°C] -10...70
Frequency end point, FEP [°C] 10...90
Frequency at the end point FRP [Hz] 100...1000
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range) ± 2 % MEW; (water)
Repeatability ± 0,5 % MEW
Temperature monitoring
Accuracy [K] ± 1
Reaction times
Flow monitoring
Response time [s] 1; (dAP = 0)
Damping process value dAP [s] 0...5
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 6
Software / programming
Parameter setting options hysteresis / window; normally open / closed; switching logic; Frequency output; switch-on/switch-off delay; Damping; Display unit
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9
Profiles Smart Sensor: Process Data Variable; Device Identification, Device Diagnosis
SIO mode yes
Required master port class A
Process data analog 2