Product characteristics
Number of inputs and outputs Number of digital outputs: 1; Number of analog outputs: 1
Measuring range
-25...160 °C -13...320 °F
Communication interface IO-Link
Process connection Ø 6 mm
Installation length EL [mm] 150
Application
System gold-plated contacts
Measuring element 1 x Pt 1000
Reference element 1 x NTC
Media liquids and gases
Pressure rating [bar] 160
Electrical data
Operating voltage [V] 18...32 DC; (cULus - Class 2 source required)
Current consumption [mA] 10; (24 V)
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 6
Integrated watchdog yes
Inputs / outputs
Number of inputs and outputs Number of digital outputs: 1; Number of analog outputs: 1
Outputs
Total number of outputs 2
Output signal analog signal; IO-Link; calibration check status
Electrical design PNP/NPN
Number of digital outputs 1
Output function normally closed; (diagnostic signal)
Max. voltage drop switching output DC [V] 2
Permanent current rating of switching output DC [mA] 100
Diagnostic output calibration check status and error diagnostics
Number of analog outputs 1
Analog current output [mA] 4...20
Max. load [Ω] (Ub - 15 V) x 50
Short-circuit protection yes
Type of short-circuit protection yes (non-latching)
Overload protection yes
Measuring/setting range
Measuring range
-25...160 °C -13...320 °F
Note on measuring range
scalable
Factory setting -10...150 °C / 14...302 °F
Calibration check limit [K] 0.5...3
In steps of [K] 0.05
Resolution
Resolution of analog output [K] 0.05
Accuracy / deviations
Precision analog output [K] ± 0,2
Precision IO-Link [K] ± 0,2
Temperature coefficient analog output [% of the span / 10 K] < ± 0,02; (In case of deviation from the reference condition 25 ± 5 °C)
Temperature coefficient IO-Link [% of the span / 10 K] < ± 0,01; (In case of deviation from the reference condition 25 ± 5 °C)
Reaction times
Dynamic response T05 / T09 [s] 1,5 / 4
Software / programming
Parameter setting options Display unit; scaling of the analog output; calibration check limit; switching logic diagnostic output; simulation mode
Interfaces
Communication interface IO-Link
Transmission type COM2 (38,4 kBaud)
IO-Link revision 1.1
SDCI standard IEC 61131-9 CDV
Profiles Digital Measuring Sensor, Common Profile, Blob Transfer
SIO mode yes
Required master port class A
Process data analog 1
Process data binary 1
Min. process cycle time [ms] 4.4
IO-Link resolution temperature [K] 0.01
Supported DeviceIDs
Type of operation DeviceID
default 1129
Operating conditions
Ambient temperature [°C] -25...70
Note on ambient temperature
max. internal device temperature: 125 °C
Storage temperature [°C] -40...100
Protection IP 68; IP 69K
Tests / approvals
EMC
DIN EN 61000-6-2
DIN EN 61000-6-3
Shock resistance
DIN EN 68000-2-27 50 g (11 ms)