Type
|
DIN-rail mounting type
|
Power voltage
|
12 to 24 VDC, Ripple (P-P)10% max.
|
Power consumption
|
Normal
|
1400 mW (For 12 V), 1600 mW (For 24 V)
|
Eco mode
|
1150 mW (For 12 V), 1350 mW (For 24 V)
|
Display method
|
4 + 1/two-digit 7-segment LED, dual-display (red/green) display (character height in the upper display (red): 8 mm 0.31", character height in the lower display (green): 5.7 mm 0.22"), Display updating cycle: 10/s
|
Operation indicator
|
Red LED x 3 (control output1/control output2/timing input indicator)
|
Display resolution
|
0.1°C or 1°C 0.2°F or 1.8°F (when using FT-H10/H20/H30), 1°C 1.8°F (when using FT-H50/H40K/H50K)
|
Hysteresis
|
Variable
|
Response speed
|
HSP, 30, 100, 200, 500, 1000, or 5000 ms can be selected (In HSP: 15 ms max.)
|
Bank selection
|
Pink and Purple wires can be configured for Bank Inputs #1,2 respectively for up to 4 total banks.
|
Bank specifications
|
Emissivity (valid in temperature mode) and limit settings x 2 can be set for each bank.
|
External input
|
Timing input
|
Input time: 2 ms min.
|
Bank input
|
Input time: 20 ms min.
|
Control output
|
PNP open collector x 2 channels (N.O./N.C. selectable), 50 mA max. (30 VDC max.), residual voltage: 1 V max.
|
Analog output
|
4 to 20 mA, maximum load resistance: 260 Ω The upper- and lower-limit values of the analog output range can be set optionally.
|
Environmental resistance
|
Ambient temperature
|
-10 to +50 °C 14 to 122 °F (No freezing)*1
|
Relative humidity
|
35 to 85 % RH (No condensation)
|
Vibration resistance
|
10 to 55 Hz, Double amplitude 1.5 mm 0.06", 2 hours in each of the X, Y, and Z axis
|
Material
|
Main unit, Cover: Polycarbonate, Keycaps: Polyester elastomer, Cable: Vinyl chloride Mounting bracket: SUS304
|
Accessory
|
DIN anchoring fixture, power cable, unit cover sticker
|
Weight
|
Approx. 85 g
|