🚚 We Ship Worldwide! Get your order delivered anywhere.🌍No Borders, Just Shipping! We deliver to your doorstep—anywhere ✈️

Brand New Partnership with DeLock!

Ifm  |  SKU: IF-SM2604-E  |  Barcode: DOES NOT APPLY

Ifm SM2604 Magnetic-Inductive Flow Meter

$1,896.00 CAD
Shipping calculated at checkout.

Ifm SM2604 Magnetic-Inductive Flow Meter is backordered and will ship as soon as it is back in stock.


🚚 We Ship Worldwide! Get your order delivered anywhere.

🌎 No Borders, Just Shipping! We deliver to your doorstep—anywhere.

Delivery And Shipping

Both Standard and Express shipping options are available at checkout.

Subscribe to our newsletter

Sign up for exclusive offers.

Industrial Automation Parts is only an authorized distributor for DeLock and is not authorized for any other manufacturers. Manufacturer's warranty and support do not apply. Our IAP warranty of three months is applicable.

Product characteristics
Number of inputs and outputs Number of analog outputs: 2
Measuring range
5...600 l/min 0.3...36 m³/h 80...9510 gph 1.3...158.5 gpm
Process connection threaded connection 2" NPT DN50
Application
System gold-plated contacts
Application empty pipe detection; for industrial applications
Media Conductive liquids; water; water-based media
Note on media
conductivity: ≥ 20 µS/cm
viscosity: < 70 mm²/s (40 °C)
Medium temperature
-10...90 °C 14...194 °F
Pressure rating [bar] 16
Pressure rating [MPa] 1.6
Pressure rating [psi] 232
MAWP (for applications according to CRN) [bar] 16
Electrical data
Operating voltage [V] 18...32 DC; (to SELV/PELV)
Current consumption [mA] < 150
Protection class III
Reverse polarity protection yes
Power-on delay time [s] 5
Inputs / outputs
Number of inputs and outputs Number of analog outputs: 2
Outputs
Total number of outputs 2
Output signal analog signal
Number of analog outputs 2
Analog current output [mA] 4...20; (≤ 22 mA)
Max. load [Ω] 500
Measuring/setting range
Measuring range
5...600 l/min 0.3...36 m³/h 80...9510 gph 1.3...158.5 gpm
Display range
-720...720 l/min -43.2...43.2 m³/h -11410...11410 gph -190.2...190.2 gpm
Resolution
0.5 l/min 0.02 m³/h 5 gph 0.1 gpm
Analog start point ASP
0...480 l/min 0...28.8 m³/h 0...7610 gph 0...126.8 gpm
Analog end point AEP
120...600 l/min 7.2...36 m³/h 1900...9510 gph 31.7...158.5 gpm
Low flow cut-off LFC
< 15 l/min < 0.9 m³/h < 240 gph < 4 gpm
In steps of
0.5 l/min 0.02 m³/h 5 gph 0.1 gpm
Measuring dynamics 1:120
Temperature monitoring
Measuring range
-20...80 °C -4...176 °F
Display range
-40...100 °C -40...212 °F
Resolution
0.2 °C 0.5 °F
Analog start point
-20...60 °C -4...140 °F
Analog end point
0...80 °C 32...176 °F
In steps of
0.2 °C 0.5 °F
Accuracy / deviations
Flow monitoring
Accuracy (in the measuring range) ± (0,8 % MW + 0,5 % MEW)
Repeatability ± 0,2% MEW
Temperature monitoring
Temperature drift ± 0,0333 °C / K; ± 0,0599 °F / K
Accuracy [K] ± 1 (25 °C; Q > 15 l/min) / ± 1 (77 °F; Q > 4 gpm)
Reaction times
Flow monitoring
Response time [s] 0.35; (dAP = 0)
Damping process value dAP [s] 0...5
Temperature monitoring
Dynamic response T05 / T09 [s] T09 = 3 (Q > 15 l/min) / T09 = 3 (Q > 4 gpm)
Software / programming
Parameter setting options display can be deactivated; Display unit; empty pipe detection
Operating conditions
Ambient temperature
-10...60 °C 14...140 °F
Storage temperature

Payment & Security

Payment methods

  • American Express
  • Apple Pay
  • Diners Club
  • Discover
  • Google Pay
  • Mastercard
  • PayPal
  • Shop Pay
  • Visa

Your payment information is processed securely. We do not store credit card details nor have access to your credit card information.

New Delock Partnership